PowerVault ML6000 Maintenance Guide 299
T098
T098 - FC I/O Blade Data Path Failure
Description GUI Description: Data path failure on Fibre Channel Blade.
Explanation: An FC I/O blade has detected a failure during the specified data
path conditioning test. This can occur if there is an error with the hardware or
the connection, or if the drive has been rebooted or is undergoing a drive
firmware update. These valid cases will be detected and will not generate this
ticket.
Detection Scenarios The data path conditioning test configured for this FC I/O blade has failed.
Root Causes Cable is not plugged in.
Cable is faulty.
Drive sled is not inserted correctly.
Service Resolution
Steps
Perform DR058 - Resolve Data Path Failure
on page 393.
Possible CRUs/FRUs Note: Read and perform all resolution steps before dispatching any parts.
Dispatch the first part listed below for replacement. If this does not solve the
problem, dispatch the second part, and so on, in order. Dispatch only one part
(or set of parts) at a time.
1 FC I/O Blade