1. Log on to the local operator panel as ADMIN. The "Network Configuration"
screen will appear.
2. Turn OFF the DHCP selection.
3. Enter the IP Address, Subnet Mask, and Default Gateway selections.
4. Verify the Library Name selection.
5. Select Apply.
6. When the SUCCESS message appears, select CANCEL. This will log OFF from
the local operator panel.
7. Log ON to the remote web browser as ADMIN. The Upgrade Notification
message should display on the web console.
8. Click on the upgrade firmware link provided, then browse to locate the
firmware file. See “Updating Library Firmware” on page 7-25 for detailed
instructions.
9. Restore the system configuration data to the compact flash card: See Appendix
E of the TS3310 Setup and Operator Guide.
Power Supply (Primary and Redundant)
1 Primary power supply 2 Redundant power supply
Library power is controlled at the individual power supplies and at the front panel
of the library. The switch on the rear of each power supply controls power for the
module in which the power supply is installed. The button on the front of the
control module controls power for all library modules in the library.
A second (redundant) power supply helps ensure that your library does not lose
power (and become inaccessible) if the primary power supply should happen to
fail. The library automatically switches to the redundant power supply if the
primary power supply fails for any reason.
A redundant power supply should be connected to a different AC circuit from the
primary power supply. Even better, the redundant power supply should be
connected to a separate power distribution source. In the event that the primary
power supply fails or becomes unstable, the redundant power supply will
automatically power the library as long as it is turned ON.