July 2013 8.1 Display and operation 1267
8.1.23 Programming station mode
You can switch the control into programming-station mode with MP7210. This
way the control can be used as a simple programming station. No drives are
enabled.
In this setting NC programs cannot be executed. You can only create and test
NC programs.
You can select whether the PLC should be active. In addition, you can activate
the emergency-stop loop if the PLC is active. The emergency-stop loop must
already be connected correctly (X41/34 and X42/4) in order to switch the
control on correctly.
If a programming-station mode is active (MP7210 > 0), this is shown in the
first line of the main menu of the PLC Programming operating mode via "MP7210
= x."
MP7210 Programming station
Input: 0: Controlling and programming
1: Programming station with PLC active
2: Programming station with PLC inactive
3: Programming station with PLC and emergency stop both
active (X41/34 and X42/4)
8.1.24 Color settings
The colors of the display unit can be defined by machine parameters.
The following color settings cannot be changed:
HEIDENHAIN logo after machine switch-on (standard color)
Error message for invalid machine parameters (red)
Blinking error message (red)
Plan view in the graphic display (blue)
Cursor (inverse)
You define the desired color by mixing the basic colors red, green and blue.
Every basic color has 256 difference stages of intensity. The input values for
color settings are byte-oriented. HEIDENHAIN recommends hexadecimal
input.
The colors can also be poorly adjusted (e.g. red error message on red
background). HEIDENHAIN therefore supplies the controls with a standard
color setting, which is suggested by the control during creation of the MP list.
Color Red Green Blue
Adjustment Rough Fine Rough Fine Rough Fine
HEX ranges 0 to F 0 to F 0 to F 0 to F 0 to F 0 to F
Input for
yellow: $0....
39 3 9 00