HEIDENHAIN iTNC 530 HSCI - Module 9173 Speed-Dependent Wye;Delta Switchover

HEIDENHAIN iTNC 530 HSCI
1966 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
July 2013 6.12 Spindle 983
Module 9173 Speed-dependent wye/delta switchover
With Module 9173, a monitoring function dependent on the speed can be
realized for the wye/delta switchover of the spindle. A switchover request is
detected by Module 9174, which supplies the current status of the wye/delta
operation. If a switchover is necessary, this is still done by Module 9163. The
actual speed is assumed during the switchover. The readiness of the current
controller is automatically rescinded when Module 9163 is called. Bit 7 of
MP2223 can be set as an alternative.
Condition:
The module should not be called cyclically. A single call is enough for
activation, deactivation or changing.
Additional information: Useful combinations for <Mode> parameter:
xx0 Deactivate monitoring
001 Monitoring on, Switchover compatible
011 Monitoring on, Accelerated but safe switchover, Wait for readiness of
current controller
111 Monitoring on, Fastest switchover possible
Call:
PS B/W/D/K <Mode>
Bit 0:
0 =Monitoring off (function deactivated)
1 =Monitoring on (automatic assumption of the actual
speed during switchover)
Bit 1:
0 =Switchover compatible to previous switchover;
switchover same as first switch-on of spindle
1 =Switchover accelerated
Bit 2:
0 =Wait for readiness of current controller
1 =Do not wait for readiness of current controller
PS B/W/D/K <Switchover speed from wye to delta operation>
PS B/W/D/K <Switchover speed from delta to wye operation>
CM 9173
Error code:
Marker Value Meaning
M4203 0 Speed-dependent monitoring active
1 Error code in W1022
W1022 1 Invalid speeds (switchover speed of wye operation
switchover speed of delta operation), or negative
speed