1318 HEIDENHAIN Technical Manual iTNC 530 HSCI
Automated testing
of drives
Faults caused by excessive leakage current or ground fault are detected only
by the UV(R) power supply unit, although the fault can also be triggered by one
of the connected power modules. The power modules must not be
disconnected for fault finding, however. It is sufficient to deactivate one axis
after the other using MP10 in order to find the axis or the power module
causing the leakage-current fault.
Information Meaning Colors
Phase 1, Phase 2,
Phase 3
Status of the phases in the
motor and the supply line
Green: Phase is OK
Red: Phase error
Leakage current Information on a short circuit
to ground in the motor, the
power module or in the
supply line
Green: No ground fault
Red: Ground fault
detected
Power module Status of the power module Green: Power module
is OK
Red: Power module
error
Supply unit Status of the supply unit Green: Supply unit OK
Red: Supply unit error
Connection Status of the connection
control power module
Green: Connection is
OK
Red: Connection error