486 HEIDENHAIN Technical Manual iTNC 530 HSCI
Module 9310 Read the machine parameter from the run-time memory
Use this module to read the value of the given machine parameter from the
run-time memory. The input value is transferred as a natural number with the
decimal point shifted by the number of possible decimal places. Machine
parameters whose contents exceed the 32-bit limit cannot be read.
A value is read from the run-time memory.
For non-indexed machine parameters, zero must be transferred as the index.
Call:
PS B/W/D/K <MP number>
PS B/W/D/K <MP index>
CM 9310
PL B/W/D <MP value/error code>
1: MP number does not exist
3: MP outside value range
6: Call was not in a submit or spawn job
7: MP is of the "string" type
8: No system memory
Error code:
Marker Value Meaning
M4203 0 MP was read
1 Error code in W1022
W1022 2 MP number does not exist or MP is outside value
range
20 Module was not called in a submit or spawn job
41 MP is of the "string" type
61 No system memory