1916 HEIDENHAIN Technical Manual iTNC 530 HSCI
10.10 Data Transfer by PLC
10.10.1 Settings
PLC modules make it possible for the PLC to transfer data via the RS-232-C/
V.24 data interface. These modules, for example, permit communication
between two MC 6xxx at PLC level via the interface.
During data transfer, use of the interface is inhibited for the input/output
program of the user interface.
Select a standard operating mode, FE1 or
Configure the data interface with MP5020.x to MP5040.x in EXT3/EXT4
mode.
MP5040 Data transfer rate in operating mode EXT3 or EXT4 (data
transfer through PLC)
Input: 0: 110 bps
1: 150 bps
2: 300 bps
3: 600 bps
4: 1200 bps
5: 2400 bps
6: 4800 bps
7: 9600 bps
8: 19200 bps
9: 38400 bps
10: 57600 bps
11: 115200 bps
MP5040.0 Operating mode EXT3 (PLC)
MP5040.1 Operating mode EXT4 (PLC)