July 2013 6.11 Monitoring functions 919
Consideration of I0 when using synchronous motors:
If I0 differs too much from Irated, then the utilization display can be adapted
via MP2312.x. In this case you must set MP2312.x = I
rated
/I
0
.
Example for the behavior of I0 and Irated with an OSY155F-EcoDyn motor:
In the diagram you can see that:
I0 = 12.8 A, Irated = 9.8 A, nRated = 3000 rpm
For the synchronous motor:
Mactl = kT · Iactl
Mrated = kT · Irated
Mrated = f(n)
Module 9166 Momentary utilization of the drive motor
The evaluation through MP2312.x is already calculated in the utilization of the
drive motor.
Call:
PS B/W/D/K <Axis>
Axis-specific: Dependence on MP4020 bit 14
CM 9166
PL B/W/D <Utilization of the drive in %>
Error code:
MP2312.x Factor for utilization of motors
Input: 0 to 1 000.000
0: Factor = 1
Marker Value Meaning
M4203 0 No error
1 Control has no current controller
0 500 1000 1500 2000 2500 3000 3500 4000
0
2
4
6
8
10
12
n [rpm]
Actual rated current [A]