1704 HEIDENHAIN Technical Manual iTNC 530 HSCI
NUMBERMP4111 = Number of required timers > 96. The corresponding number of machine
parameters MP4111.96 to MP4111.x is created.
Input example: NUMBERMP4111 = 10
(Machine parameters MP4111.96 to MP4111.105 are created.)
NUMBERMP4230 = Sets a number in the PLC for Module 9032. The corresponding number of
machine parameters MP4230.x is created. The maximum input value is 99; no
entry or an invalid entry defines 32 indexes.
Input example: NUMBERMP4230 = 40
(Machine parameters MP4230.0 to MP4230.40 are created.)
OEMCYC.
ZIPNAME =
The possibility of machining with or without preset tables can also be used in
OEM cycles. A separate directory is created on the PLC partition for each cycle
project (PLC:\OEMCYC_ZIP\, PLC:\OEMCY2_ZIP\, etc.). In OEM.SYS, enter
after the keyword the name of the *.ZIP file to be unpacked, e.g.
OEMCYC.ZIPNAME = ABC.ZIP, OEMCY2.ZIPNAME = DEF.ZIP, etc. The *.ZIP files
contain all information for the cycles, including the directory structure. When
the control is started up, the appropriate *.ZIP files are unpacked in the folders.
The documentation for CycleDesign contains more detailed information.
PALETTPRESET = Activate pallet preset table in order to manage reference points for pallets, see
page 1495
Input example: PALLETPRESET = TNC:\Palletpreset.pr
PLCCOMPCFG = Configuration file for conditional compiling.
Input example: PLCCOMPCFG = PLC:\OEM\OEM.CFG
PLCDIALOG = Name for text file with PLC dialogs; the path for the text file is permanently
defined.
Input example: PLCDIALOG = DIALOG.A
PLCERRFIX = Path for "Corrective action" help text.
Input example: PLCERRFIX = FIX.A
PLCERROR = Name for text file with PLC error messages; the path for the text file is
permanently defined.
Input example: PLCERROR = PLC_ERR.A
PLCERRREASON = Path for "Cause of error" help text.
Input example: PLCERRREASON = REASON.A