Cisco ONS 15454 SDH Procedure Guide, R7.0
78-17194-01
Chapter 4 Turn Up a Node
NTP- D24 Verify Card Installation
11. NTP-D326 Provision OSI, page 4-14—Complete this procedure if the ONS 15454 SDH will be
connected in networks with network elements (NEs) that are based on the Open System
Interconnection (OSI) protocol stack. This procedure provisions the Target Identifier Address
Resolution Protocol (TARP), OSI routers, manual area addresses, subnetwork points of attachment,
and IP-over-OSI tunnels.
NTP-D24 Verify Card Installation
Step 1 Verify that two TCC2/TCC2P cards are installed in Slots 7 and 11.
Step 2 Verify that the green ACT (active) LED is illuminated on one TCC2/TCC2P card and the amber STBY
(standby) LED is illuminated on the second TCC2/TCC2P card.
Note If the TCC2/TCC2P cards are not installed, or if their LEDs are not operating as described, do
not proceed. Repeat the “DLP-D332 Install the TCC2/TCC2P Cards” task on page 20-22, or
refer to the Cisco ONS 15454 SDH Troubleshooting Guide to resolve installation problems
before proceeding to Step 3.
Step 3 Verify that cross-connect cards (XC-VXL-2.5G, XC-VXL-10G, XC-VXC-10G) are installed in Slots 8
and 10. The cross-connect cards must be the same type.
Step 4 Verify that the green ACT (active) LED is illuminated on one cross-connect card and the amber STBY
(standby) LED is illuminated on the second cross-connect card.
Note If the cross-connect cards are not installed, or if their LEDs are not illuminated as described, do
not proceed. Repeat the “DLP-D333 Install the XC-VXL-10G, XC-VXL-2.5G, or
XC-VXC-10G Cards” task on page 20-25, or refer to the Cisco ONS 15454 SDH
Troubleshooting Guide to resolve installation problems before proceeding to Step 5.
Step 5 If your site plan requires an AIC-I card, verify that the AIC-I card is installed in Slot 9 and its ACT
(active) LED displays a solid green light.
Step 6 Verify that electrical cards (E1-N-14, E1-42, E3-12, DS3I-N-12, or STM1E) are installed in the
ONS 15454 SDH slots as designated by your installation plan.
Step 7 If your site plan requires an Ethernet card, verify that the Ethernet card is installed in the specified slot
and its ACT (active) LED displays a solid green light:
• The E100T-12, E100T-12-G, E1000-2, E1000-2-G, G1K-4, ML1000-2, ML100T-12, ML-100X-8,
and CE-1000-4 cards are installed in Slots 1 to 6 or 12 to 17.
Purpose This procedure verifies that the ONS 15454 SDH node is ready for turn-up.
Tools/Equipment An engineering work order, site plan, or other document specifying the
ONS 15454 SDH card installation.
Prerequisite Procedures Chapter 1, “Install the Shelf and FMECs”
Chapter 2, “Install Cards and Fiber-Optic Cable”
Required/As Needed Required
Onsite/Remote Onsite
Security Level Retrieve or higher