21-16
Cisco ONS 15454 SDH Procedure Guide, R7.0
78-17194-01
Chapter 21 DLPs D400 to D499
DLP- D431 Discontinue Alarm Suppression
• If the card is an ML-Series Ethernet card, click the Provisioning > Ether Alarming >
Alarm Behavior tabs or the Provisioning > POS Alarming > Alarm Behavior tabs, depending on
whether you want to apply the profile to the front physical ports (“Ether alarming”) or packet over
SDH (“POS alarming”). For more information about ML-Series card ports and service, see the
Ethernet Card Software Feature and Configuration Guide for the Cisco ONS 15454,
Cisco ONS 15454 SDH, and Cisco ONS 15327.
Step 6 Check the Suppress Alarms column check box for the port row where you want to suppress alarms
(Figure 21-4 on page 21-10).
Step 7 Click Apply.
Alarms that apply directly to this port change appearance as described in Step 2. (However, alarms
raised on the entire card will remain raised.) A raised AS-CMD alarm that shows the port as its object
appears in either alarm window. For example, if you suppressed alarms for Port 1 on the Slot 16 STM-3
card, the alarm object will be FAC-16-1.
Step 8 Return to your originating procedure (NTP).
DLP-D431 Discontinue Alarm Suppression
Caution If multiple CTC sessions are open, discontinuing suppression in one session will discontinue
suppression in all other open sessions.
Step 1 To discontinue alarm suppression for the entire node:
a. In node view, click the Provisioning > Alarm Profiles > Alarm Behavior tabs.
b. Uncheck the Suppress Alarms check box.
Suppressed alarms will reappear in the Alarms window. (They might have previously been cleared from
the window using the Synchronize button.) The AS-CMD alarm with the System object will be cleared
in all views.
Step 2 To discontinue alarm suppression for individual cards:
a. In the node view, click the Provisioning > Alarm Profiles > Alarm Behavior tabs.
b. Locate the card that was suppressed in the slot list.
c. Uncheck the Suppress Alarms column check box for that slot.
d. Click Apply.
Purpose This task discontinues alarm suppression and reenables alarm reporting on
a port, card, or node.
Tools/Equipment None
Prerequisite Procedures DLP-D430 Suppress Alarm Reporting, page 21-15
DLP-D60 Log into CTC, page 17-49
Required/As Needed As needed
Onsite/Remote Onsite or remote
Security Level Provisioning or higher