20-26
Cisco ONS 15454 SDH Procedure Guide, R7.0
78-17194-01
Chapter 20 DLPs D300 to D399
DLP- D334 Install the Alarm Interface Controller–International Card
Step 7 Verify that the card is inserted correctly and close the latches/ejectors on the card.
Note It is possible to close the latches/ejectors when the card is not completely plugged into the
backplane. Ensure that you cannot insert the card any further.
Step 8 Verify the LED activity:
• The red LED turns on for 20 to 30 seconds.
• The red LED blinks for 35 to 45 seconds.
• The red LED remains on for 5 to 10 seconds.
• All LEDs blink once and turn on.
• The ACT/STBY LED turns on.
Note If you insert a card into a slot provisioned for a different card, all LEDs turn off.
Note If the red FAIL LED does not turn on, check the power.
Note If the red FAIL LED is on continuously or the LEDs act erratically, the card is not installed
properly. Remove the card and repeat Steps 6 to 8.
Step 9 Verify that the ACT/STBY LED is amber for standby.
Step 10 Return to your originating procedure (NTP).
DLP-D334 Install the Alarm Interface Controller–International Card
Step 1 Open the latches/ejectors on the card.
Step 2 Use the latches/ejectors to firmly slide the card along the guide rails until the card plugs into the
receptacle at the back of the slot (Slot 9).
Step 3 Verify that the card is inserted correctly and close the latches/ejectors on the card.
Purpose This task installs the AIC-I card. The AIC-I card provides connections for
external alarms and controls (environmental alarms).
Tools/Equipment AIC-I card
Prerequisite Procedures DLP-D332 Install the TCC2/TCC2P Cards, page 20-22
DLP-D333 Install the XC-VXL-10G, XC-VXL-2.5G, or XC-VXC-10G
Cards, page 20-25
Required/As Needed As needed
Onsite/Remote Onsite
Security Level None