9-9
Cisco ONS 15454 SDH Procedure Guide, R7.0
78-17194-01
Chapter 9 Manage Alarms
NTP- D247 Provision External Alarms and Controls on the Alarm Interface Controller–International
Step 6 Click Apply.
Step 7 If you are provisioning external alarms, click the External Alarms tab (Figure 9-3). If you are not
provisioning external alarms, skip Steps 8 through 10 and go to Step 11.
Figure 9-3 Provisioning External Alarms on the AIC-I Card
Step 8
Complete the following fields for each external device wired to the ONS 15454 SDH backplane:
• Enabled—Check the check box to activate the fields for the alarm input number.
• Alarm Type—Choose an alarm type from the drop-down list.
• Severity—Choose a severity from the drop-down list.
The severity determines the severity the alarm has in the Alarms and History tabs and determines
whether the LEDs are activated. Critical (CR), Major (MJ), and Minor (MN) alarms activate the
LEDs. Not Alarmed (NA) and Not Reported (NR) do not activate LEDs, but do report the
information in CTC.
• Virtual Wire—Choose the virtual wire number from the drop-down list to assign the external device
to a virtual wire. Otherwise, do not change the default (None). For information about the AIC-I
virtual wire, see the “Alarm Monitoring and Management” chapter in the Cisco ONS 15454 SDH
Reference Manual.
• Raised When—From the drop-down list, choose the contact condition (open or closed) that triggers
the alarm.
• Description—A default description is provided; enter a different description if needed.
Step 9 To provision additional devices, complete Step 8 for each additional device.
Step 10 Click Apply.