3-3
Cisco ONS 15454 SDH Procedure Guide, R7.0
78-17194-01
Chapter 3 Connect the PC and Log into the GUI
NTP- D260 Set Up CTC Computer for Local Craft Connection to the ONS 15454 SDH
NTP-D260 Set Up CTC Computer for Local Craft Connection to the
ONS
15454 SDH
Step 1 Complete one of the CTC computer setup tasks listed in Table 3-1 based upon your CTC connection
environment.
Purpose This procedure explains how to set up a PC running Windows or a Solaris
workstation for an onsite local craft connection to the ONS 15454 SDH.
Tools/Equipment Network interface card (NIC), also referred to as an Ethernet card
Straight-through (CAT-5) LAN cable
Prerequisite Procedures NTP-D278 Set Up Computer for CTC, page 3-2
Required/As Needed As needed
Onsite/Remote Onsite or remote
Security Level None
Table 3-1 CTC Computer Setup for Local Craft Connection to the ONS 15454 SDH
CTC Connection Environment CTC Computer Setup Task
• You are connecting from a Windows PC.
• You will connect to one ONS 15454 SDH.
• You need to access non-ONS 15454 SDH applications
such as ping and tracert (trace route).
DLP-D50 Set Up a Windows PC for Craft
Connection to an ONS 15454 SDH on the
Same Subnet Using Static IP Addresses,
page 17-37
• You are connecting from a Windows PC.
• The CTC computer is provisioned for Dynamic Host
Configuration Protocol (DHCP).
• The ONS 15454 SDH has DHCP forwarding enabled.
• The ONS 15454 SDH is connected to a DHCP server.
Note The ONS 15454 SDH does not provide IP
addresses. If DHCP is enabled, it passes DCHP
requests to an external DHCP server.
DLP-D51 Set Up a Windows PC for Craft
Connection to an ONS 15454 SDH Using
Dynamic Host Configuration Protocol,
page 17-39
Note Do not use this task for initial
node turn-up. Use the task only if
DHCP forwarding is enabled on
the ONS 15454 SDH. By default,
DHCP is not enabled. To enable
it, see the “NTP-D169 Set Up
CTC Network Access” procedure
on page 4-7.