Cisco ONS 15454 SDH - Troubleshooting MXP, TXP, or FC_MR Circuit Paths With Loopbacks

Cisco ONS 15454 SDH
860 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1-14
Cisco ONS 15454 SDH Procedure Guide, R7.0
78-17194-01
Chapter 1 Install the Shelf and FMECs
NTP- D222 Install the E1-75/120 Conversion Panel
Figure 1-3 Mounting the E1-75/120 Conversion Panel in a Rack
Step 2
Align the screw holes on the mounting ears with the mounting holes in the rack.
Step 3 Install one mounting screw in each side of the assembly.
Step 4 When the E1-75/120 conversion panel is secured to the rack, install the remaining mounting screws if
necessary.
Step 5 Continue with the “NTP-D223 Attach Wires to Alarm, Timing, LAN, and Craft Pin Connections”
procedure on page 1-15.
Stop. You have completed this procedure.
83912
Equipment rack