Cisco ONS 15454 SDH Procedure Guide, R7.0
78-17194-01
Chapter 1 Install the Shelf and FMECs
NTP- D6 Install the Power and Ground
NTP-D6 Install the Power and Ground
Warning
Before performing any of the following procedures, ensure that power is removed from the DC circuit.
Statement 1003
Warning
This equipment is intended to be grounded. Ensure that the host is connected to earth ground during
normal use.
Statement 39
Warning
Use copper conductors only.
Statement 1025
Warning
Connect the unit only to DC power source that complies with the safety extra-low voltage (SELV)
requirements in IEC 60950 based safety standards.
Statement 1033
Warning
This product requires short-circuit (overcurrent) protection, to be provided as part of the building
installation. Install only in accordance with national and local wiring regulations.
Statement 1045
Purpose This procedure installs power feeds and grounds the ONS 15454 SDH.
Tools/Equipment #2 Phillips screwdriver
Medium slot-head screwdriver
Small slot-head screwdriver
Screws
Power cable (from fuse panel to MIC-A/P and to MIC-C/T/P), shipped with
the ONS 15454 SDH
Ground cable 13.3-mm² (#6 AWG) stranded
Two-hole grounding lug, shipped with the ONS 15454 SDH
Listed pressure terminal connectors such as ring and fork types; connectors
must be suitable for 8.36-mm² (#8 AWG) copper conductors
Wire cutters
Wire strippers
Crimp tool
Fuse panel
Prerequisite Procedures NTP-D219 Open and Remove the FMEC Cover, page 1-7
NTP-D220 Install the Power and Signal FMECs, page 1-7 (for MIC-A/P
and MIC-C/T/P)
Required/As Needed Required
Onsite/Remote Onsite
Security Level None