20-12
Cisco ONS 15454 SDH Procedure Guide, R7.0
78-17194-01
Chapter 20 DLPs D300 to D399
DLP- D324 Install Alarm Cables on the MIC-A/P
Figure 20-4 Removing the ONS 15454 SDH FMEC Cover
Step 4
Detach the cover from the pin of the hinge.
Step 5 Remove the cover carefully from the left pin of the hinge.
Step 6 Return to your originating procedure (NTP).
DLP-D324 Install Alarm Cables on the MIC-A/P
Step 1 Using 0.51 mm² or 0.64 mm² (#22 or #24 AWG) wires, connect the alarm and control wires on the
appropriate pins of the DB-62 connector. The pin connectors, signal names, and functions are listed in
Table 20-1.
Purpose This task installs alarm cables on the MIC-A/P FMEC so that you can
provision external (environmental) alarms and controls with the AIC-I
card.
Tools/Equipment DB-62 connector
0.51 mm² or 0.64 mm² (#22 or #24 AWG) wires
Prerequisite Procedures NTP-D220 Install the Power and Signal FMECs, page 1-7
Required/As Needed As needed
Onsite/Remote Onsite
Security Level None