A-4
Cisco ONS 15454 DWDM Reference Manual, R8.5
78-18343-02
Appendix A      Hardware Specifications
A.1.11    System Power
 • Free running accuracy: +/– 4.6 ppm
 • Holdover stability: 3.7 x 10
–7
 per day, including temperature (< 255 slips in first 24 hours)
 • Reference: External BITS, line, internal
The ONS 15454 ETSI has the following system timing specifications: 
 • Stratum 3E, per ITU-T G.813
 • Free running accuracy: +/– 4.6 ppm
 • Holdover stability: 3.7 exp –7 per day, including temperature (< 255 slips in first 24 hours)
 • Reference: External BITS, line, internal
A.1.11 System Power
The ONS 15454 ANSI has the following power specifications: 
 • Nominal Input Voltage: –48 VDC
 • Power consumption: Configuration dependent; 55 W (fan tray only)
 • Power requirements: 
 –
Nominal: –48 VDC 
 –
Input Voltage Range: –40.5 to –57.0 VDC
 • Power terminals: #6 Lug
 • ANSI shelf fusing: 100–A fuse panel (minimum 30 A fuse per shelf) 
HD shelf fusing: 100–A fuse panel (minimum 30 A fuse per shelf)
The ONS 15454 ETSI has the following power specifications: 
 • Nominal Input Voltage: –48 VDC
 • Power consumption: Configuration dependent; 53 W (fan tray only)
 • Power requirements: 
 –
Nominal: –48 VDC
 –
Input Voltage Range: –40.5 to –57.0 VDC
 • Power terminals: 3WK3 Combo-D power cable connector (MIC-A/P and MIC-C/T/P faceplates)
 • Fusing: 100 A fuse panel; minimum 30 A fuse per shelf
A.1.12 Fan Tray
Table A-1 lists power requirements for the fan-tray assembly.
Table A-1 Fan Tray Assembly Power Requirements
Fan Tray Assembly Watts Amps BTU/Hr
FTA2 
53 1.21 198
FTA3 -T
86.4 1.8 295
15454E-CC-FTA/15454-CC-FTA
115 2.4 393