Upgrade and Maintenance Manual TX2560 M2 / RX2560 M2
12.5.3 Replacing a slimline ODD or LSD
12.5.3.1 Preliminary steps
Ê
"Locating the defective server" on page 55
Ê
"Removing backup and optical disk media" on page 114
Ê
"Shutting down the server" on page 58
Ê
"Disconnecting the power cord" on page 59
Ê
"Getting access to the component" on page 61
I
Removing the front cover is not required in order to replace the
slimline ODD or LSD in the Multibay box.
Ê
"Removing the system air duct" on page 91
Ê
"Removing the system fan holder" on page 93
Ê
"Removing the Multibay box" on page 411
12.5.3.2 Removing the defective slimline ODD
Ê
Remove the slimline ODD from the Multibay box as described in section
"Removing the slimline ODD from the Multibay box" on page 412.
12.5.3.3 Removing the defective LSD module
Ê
Remove the LSD module from the Multibay box as described in section
"Removing the LSD module from the Multibay box" on page 414.
Upgrade and Repair Unit
(URU)
Hardware: 10 minutes
Tools:
– Phillips PH2 / (+) No. 2 screw driver
– Slotted screw driver (for bending in or out accessible drive
mounting brackets)