Migrating from a DEFINITY Server CSI in a CMC with an ATA Flash to an S8400 Media Server
382 Upgrading, Migrating, and Converting Media Servers and Gateways
Upgrading firmware
Each TN8412AP S8400 IP Interface (SIPI) circuit pack must be on the most current and same
firmware load. You might need to upgrade the firmware on the SIPI. The most current firmware
load is on the installation CD. To obtain the firmware, you also can go to Avaya Support Web
page at (http://avaya.com/support
and click Downloads.
First, verify the version of firmware that is currently on the SIPI circuit pack.
1. Under Installation and Upgrades, click View IPSI Version. Select Query All and click View
IPSI Version.
2. Verify the firmware release for the TN8412AP SIPI circuit pack.
If necessary, upgrade the firmware on the just installed SIPI circuit pack that you just installed.
For more information, see Upgrading firmware on the IPSIs and SIPIs
on page 283.
You also must upgrade the firmware on the following circuit packs, if necessary.
● UDS1 (TN464GP, TN2464BP, and TN2313AP)
● Maintenance/Test (TN771DP)
● Control LAN (C-LAN) (TN799DP)
● IP Media Processor (TN2302AP)
For more information, see Upgrading firmware on the IPSIs and SIPIs
on page 283.
Testing the installation
Test the complete installation. For more information, see Testing the Complete Configuration on
the Documentation for Avaya Communication Manager Release 3.0, Media Gateways and
Servers CD-ROM.
Busying out previously busied out trunks
If you recorded any busyouts earlier on the main server only, you need to ensure that they also
are busied out after the conversion.
Troubleshooting the migration
For more information, see Troubleshooting an Installation on the Documentation for Avaya
Communication Manager Release 3.0, Media Gateways and Servers CD-ROM.