Post-migration administration
Issue 2.1 June 2006 859
Installing TN771 Maintenance/Test circuit pack
You must replace the TN798 or the TN2402 circuit pack with a TN771 Maintenance/Test circuit
pack. Each location must have one TN771 Maintenance/Test circuit pack.
To install the TN771 Maintenance/Test circuit pack:
● Install the TN771 circuit pack in slot 1.
This carrier does not have a dedicated slot for the TN775 Maintenance (EPN) circuit pack.
Connecting to the media server
To connect to the media server:
1. Connect one end of the green CAT5 straight-through cable to the Ethernet switch on the
customer network.
2. Connect the other end of the cable to the IPSI adapter on the back of the media gateway.
Post-migration administration
Accessing the server command line interface with SSH protocol
Note:
Note: Using the SSH protocol to access the server is applicable to CM Release 3.0 and
forward.
To use this procedure with a laptop cable connection to the services port, you must configure
your laptop for the network connection. See Network configuration
on page 1242. In addition, a
third-party SSH client must already be installed on your computer.
PuTTY is one such client available for download from http://www.putty.nl/download.html
. The
following procedure describes, as an example of SSH access, how to log into the server
command line with PuTTY.