EasyManua.ls Logo

Sel 411L - Table 3.169 Secondary Impedances

Sel 411L
1108 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
P.3.333
Date Code 20151029 Protection Manual SEL-411L Relay
Protection Functions
Protection Application Examples
Use the data from Table 3.168 to calculate the secondary impedances listed in
Table 3.169.
Application Summary
This application is for a single circuit breaker with three-pole tripping and the
following protection functions:
Line current differential protection with line-charging current
compensation
Master/outstation operation
Overcurrent backup protection
Relay settings that this example does not mention do not apply to this
application example.
Line impedance
Z1L1 = Z1L2 = Z1L3
Z0L1 = Z0L2 = Z0L3
B1L1 = B1L2 = B1L3
B0L1 = B0L2 = B0L3
0.55 / mile 86.15° primary
2.07 / mile 73.29° primary
7.79 S / mile primary
4.80 S / mile primary
Transformer
MVA
Leakage Reactance
Connection
Ratio
225
8%
YDAB
345/69 kV
Source S Impedance
Z1S = Z0S 24 87° primary
Source R Impedance
Z1R = Z0R 18 87° primary
Source T Impedance
Z1T = Z0T 20 87° primary
Maximum line current 1000 A 10°
PTR (Potential transformer ratio) 345 kV: 115 V = 3000
At terminals S and R
Current transformer ratio
CT class (both)
Burden (both)
At terminal T
Current transformer ratio
CT class
Burden
S = 1000:5 = 200, R = 800:5 = 160
C800
1.5
2000:1 = 2000 (Phase)
100:1= 100 (Neutral)
C400
2.5
Phase rotation ABC
Table 3.169 Secondary Impedances
Parameter Value
Line Susceptance (Terminal S = Terminal R)
B1L (L1 + L2 + L3)
B0L (L1 + L2 + L3)
26.9 mS
16.5 mS
Table 3.168 System Data—345 kV Overhead Transmission Line (Sheet 2 of 2)
Parameter Value

Table of Contents

Related product manuals