P.15.38
SEL-411L Relay Protection Manual Date Code 20151029
ASCII Command Reference
Description of Commands
MET SYN
Use the MET SYN command to view the synchronism-check reference
voltage, normalized source voltages, angles, and slip calculations.
If you have not enabled the synchronism-check function, the relay responds,
Synchronism Check Element Is Not Available. (Enable synchronism
check with the Global settings E25BK1, E25BK2, and NUMBK; see
Section 4: Autoreclosing and Synchronism-Check and Section 5: Settings).
MET T
Use the MET T command to view the temperature data from the SEL-2600A
RTD Module. This command requires setting PROTO = RTD for the serial
port connected to the SEL-2600A RTD Module.
The relay displays the number of RTD channels specified by the RTDNUM
Port Setting. If the RTD protocol is not enabled on any of the relay ports, the
relay displays the following:
No data available
If there is a communications failure between the relay and the SEL-2600A, as
indicated by the RTDCOMF Relay Word bit, the relay displays the following:
Communication Failure
If the RTDFL Relay Word bit is set to indicate a SEL-2600A failure, the relay
displays the following:
SEL-2600 Failure
If any of the RTDxTY Port Settings are set to NA, the relay displays the
following for that channel:
Channel Not Used
If the RTDxxST Relay Word bit is set for any of the RTDNUM channels being
reported, the relay displays the following:
Channel Failure
Table 15.94 MET RTC Command
Command Description Access Level
MET RTC Display received synchrophasor client data 1, B, P, A, O, 2
MET RTC k Display received synchrophasor client data k times 1, B, P, A, O, 2
Ta b l e 1 5.95 M E T SY N Co m m a n d
Command Description Access Level
MET SYN Display the synchronism-check values. 1, B, P, A, O, 2
MET SYN k Display the synchronism-check values
successively for k times.
1, B, P, A, O, 2
Ta b l e 1 5.9 6 M E T T Co m m a nd
Command Description Access Level
MET T Display up to 12 temperature analog values from the
SEL
-2600A RTD Module.
1, B, P, A, O, 2
MET T k Display up to 12 temperature analog values from the
SEL
-2600A RTD Module successively for k times.
1, B, P, A, O, 2