P.4.47
Date Code 20151029 Protection Manual SEL-411L Relay
Autoreclosing and Synchronism-Check
Settings and Relay Word Bits for Autoreclosing and Manual Closing
3P1CLS Three Pole BK 1 Reclose Supervision
(SELOGIC Equation)
b
1
3P2CLS Three Pole BK 2 Reclose Supervision
(SEL
OGIC Equation)
b
1
Voltage Elements
EVCK Reclosing Voltage Check (Y, N) N
27LP Dead Line Voltage (1.0–200 V secondary) 14.0
59LP Live Line Voltage (1.0–200 V secondary) 53.0
27BK1P Breaker 1 Dead Busbar Voltage
c
(1.0–200 V secondary) 14.0
59BK1P Breaker 1 Live Busbar Voltage
c
(1.0–200 V secondary) 53.0
27BK2P Breaker 2 Dead Busbar Voltage
c
(1.0–200 V secondary) 14.0
59BK2P Breaker 2 Live Busbar Voltage
c
(1.0–200 V secondary) 53.0
a
Adjust all timers in 1-cycle steps.
b
These settings cannot be set to NA or to logical 0.
c
These settings must be made on the normalized voltage scale if setting KS1M 1.00 or
KS2M 1.00 (see Voltage Magnitude and Angle Compensation).
Table 4.25 Autoreclose Logic Relay Word Bits (Sheet 1 of 2)
Name Description
BK1RS Breaker 1 in Reset State
BK2RS Breaker 2 in Reset State
79CY1 Relay in Single-Pole Reclose Cycle State
79CY3 Relay in Three-Pole Reclose Cycle State
BK1LO Breaker 1 in Lockout State
BK2LO Breaker 2 in Lockout State
SPARC Single-Pole Reclose Initiate Qualified
SPOISC Single-Pole Open Interval Supervision Condition
SPOI Single-Pole Open Interval Timing
SPSHOT0 Single-Pole Shot Counter = 0
SPSHOT1 Single-Pole Shot Counter = 1
SPSHOT2 Single-Pole Shot Counter = 2
SPLSHT Single-Pole Reclose Last Shot
SPRCIP Single-Pole Reclaim In-Progress
3PARC Three-Pole Reclose Initiate Qualified
3POISC Three-Pole Open Interval Supervision Condition
3POI Three-Pole Open Interval Timing
3PSHOT0 Three-Pole Shot Counter = 0
3PSHOT1 Three-Pole Shot Counter = 1
3PSHOT2 Three-Pole Shot Counter = 2
3PSHOT3 Three-Pole Shot Counter = 3
3PSHOT4 Three-Pole Shot Counter = 4
3PLSHT Three-Pole Reclose Last Shot
3PRCIP Three-Pole Reclaim In-Progress
Table 4.24 Autoreclose Logic Settings
a
(Sheet 3 of 3)
Label Prompt Default Value