P.15.36
SEL-411L Relay Protection Manual Date Code 20151029
ASCII Command Reference
Description of Commands
MET M
Use the MET M command to view power system maximum and minimum
quantities.
The reset command, MET RM, resets the Line, BK1, and BK2 maximum/
minimum metering quantities. When you issue the MET RM command, the
relay responds,
Reset Max/Min Metering (Y/N)? If you answer Y <Enter>,
the relay responds,
Max/Min Reset.
MET PM
Use the MET PM command to view the time-synchronized line quantities.
The relay must be in the high-accuracy timekeeping HIRIG mode. For more
information on high-accuracy timekeeping, see Configuring High-Accuracy
Timekeeping on page P.13.1.
If the relay is not in the high-accuracy IRIG (HIRIG) timekeeping mode, it
will respond to the MET PM command with the following message:
Aborted: A High Accuracy Time Source is Required
If Global enable setting EPMU := N, the relay will respond to the MET PM
command with:
Synchronized phasor measurement is not enabled
To request a report of the synchrophasor data at a specific time, enter the
optional time parameter as a time of day. For example, the relay will respond
to the MET PM 16:40:10 command with:
Synchronized Phasor Measurement Data Will Be Displayed at
16:40:10.000
Table 15.90 MET M Command
Command
a
a
Parameter n is 1 or 2 to indicate Circuit Breaker 1 or Circuit Breaker 2.
Description Access Level
MET M Display Line maximum/minimum metering
data.
1, B, P, A, O, 2
MET M k Display Line maximum/minimum metering
data successively for k times.
1, B, P, A, O, 2
MET BKn M Display Breaker n maximum/minimum
metering data.
1, B, P, A, O, 2
MET BKn M k Display Breaker n maximum/minimum
metering data successively for k times.
1, B, P, A, O, 2
MET RM Reset maximum/minimum metering data. P, A, O, 2
Ta b l e 1 5.9 1 M E T P M C o m m a n d
Command Description Access Level
MET PM Display time-synchronized line values. 1, B, P, A, O, 2
MET PM k Display time-synchronized line values
successively for k times.
1, B, P, A, O, 2
MET PM time Display time-synchronized line values
captured at trigger time.
1, B, P, A, O, 2
MET PM HIS Display time-synchronized line values
captured for the previous MET PM command.
1, B, P, A, O, 2