EasyManua.ls Logo

Sel 411L - Figure 8.15 Sample Compressed ASCII Summary

Sel 411L
1108 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
P.8.28
SEL-411L Relay Protection Manual Date Code 20151029
Oscillography, Events, and SER
Event Reports, Event Summaries, and Event Histories
CSUMMARY
The relay outputs a Compressed ASCII summary report for SCADA and other
automation applications. Issue ASCII command CSU to view the Compressed
ASCII summary report. A sample of the summary report appears in
Figure 8.15; this is a comma-delimited ASCII file. The relay appends a four-
digit hex checksum at the end of the lines in the Compressed ASCII report.
Items included in the Compressed ASCII summary report are similar to those
included in the summary report, although the relay reports the items in a
special order. For the purpose of improving products and services, SEL
sometimes changes the items and item order.
Figure 8.15 Sample Compressed ASCII Summary
Event History
The event history gives you a quick look at recent relay activity. The relay
labels each new event with a unique number from 10000 to 42767. (At 42767
the relay returns to 10000 for the next event number and then continues to
increment.) See Figure 8.16 for a sample event history.
The event history contains the following:
Standard report header
Relay and terminal identification
Date and time of report
Event number
Event date and time
Event type
Location of fault (if applicable)
Maximum phase current from summary fault data
Active group at the trigger instant
Targets
Figure 8.16 is a sample event history from a terminal.
=>>CSU <Enter>
"RID","SID","FID","03e2"
"Relay 1","Station A","SEL-411L-1-X256-V0-Z003002-D20120601","0eb0"
"EVENT_NUM","MONTH","DAY","YEAR","HOUR","MIN","SEC","MSEC","USEC","EVENT","LOCATION","FROM","FLM"
,"TIME_SOURCE","SHOT_1P","SHOT_3P","FREQUENCY","GROUP","BREAKER1","HOUR_T1","MIN_T1","SEC_T1"
,"MSEC_T1","HOUR_C1","MIN_C1","SEC_C1","MSEC_C1","BREAKER2","HOUR_T2","MIN_T2","SEC_T2","MSEC
_T2","HOUR_C2","MIN_C2","SEC_C2","MSEC_C2","T_LED1","T_LED2","TARGETS","MB_TRIGGER","MB_TRIP"
,"IA_PF
","IA_DEG_PF","IB_PF","IB_DEG_PF","IC_PF","IC_DEG_PF","IG_PF","IG_DEG_PF","3I2_PF","3I2_DEG_PF","
I1_PF","I1_DEG_PF","VA_PF","VA_DEG_PF","VB_PF","VB_DEG_PF","VC_PF","VC_DEG_PF","VS1_PF","VS1_
DEG_PF","VS2_PF","VS2_DEG_PF","V1MEM_PF","V1MEM_DEG_PF","V0_PF","V0_DEG_PF","V2_PF","V2_DEG_P
F","V1_PF","V1_DEG_PF","IA","IA_DEG","IB","IB_DEG","IC","IC_DEG","IG","IG_DEG","3I2","3I2_DEG
","I1","I1_DEG","VA","VA_DEG","VB","VB_DEG","VC","VC_DEG","VS1","VS1_DEG","VS2","VS2_DEG","V1
MEM","V1MEM_DEG","V0","V0_DEG","V2","V2_DEG","V1","V1_DEG","IA_PFD","IA_DEG_PFD","IB_PFD","IB
_DEG_PFD","IC_PFD","IC_DEG_PFD","IQ_PFD","IQ_DEG_PFD","IG_PFD","IG_DEG_PFD","IA_D","IA_DEG_D"
,"IB_D","IB_DEG_D","IC_D","IC_DEG_D","IQ_D","IQ_DEG_D","IG_D","IG_DEG_D","10F6"
10000,6,7,2012,9,50,47,335,700,"TRIG","$$$$.$$","LOCAL","SE","OTHER",0,0,60.00,1,"OPEN", , , , , ,
, , ,"NA", , , , , , , , ,0,0," ","0000000000"," ",1,-52.81,1,-157.30,1,86.35,0,-106.99,0,-
75.38,1,-42.35,0.019,93.23,0.023,9.66,0.017,-
114.85,0.038,173.89,0.016,71.89,0.000,45.52,0.006,26.99,0.004,-
11.40,0.019,116.87,0,0.00,0,106.60,0,21.15,0,35.03,0,94.06,0,-
96.33,0.005,96.68,0.005,11.32,0.003,162.80,0.007,-155.05,0.003,-
151.28,0.000,45.52,0.002,76.79,0.002,-
116.95,0.004,99.15,0.00,0.00,0.00,0.00,0.00,0.00,0.00,0.00,0.00,0.00,0.00,0.00,0.00,0.00,0.00
,0.00,0.00,0.00,0.00,0.00,"6D03"
=>>