P.1.6
SEL-411L Relay Protection Manual Date Code 20151029
Introduction and Specifications
Models and Options
INT7:
Contact inputs: 8 independent inputs (level sensitive
and optoisolated);
Contact outputs: 13 High-Current Interrupting Form A
and 2 standard Form C outputs
INTE:
Contact inputs: 8 independent inputs (level sensitive
and optoisolated);
Contact outputs: 8 High-Speed, High-Current
Interrupting (polarity sensitive) Form A outputs
Chassis orientation and type
Horizontal rack mount
Horizontal panel mount
Vertical rack mount
Vertical panel mount
Power supply
48–125 Vdc or 110–120 Vac
125–250 Vdc or 120–240 Vac
Secondary inputs
1 A nominal or 5 A nominal CT inputs
300 V phase-to-neutral wye configuration PT inputs
Ethernet card options
Ethernet card with port combinations of:
Four copper (10BASE-T/100BASE-TX)
Four fiber (100BASE-FX)
Two sets:
Copper (10BASE-T/100BASE-TX)
Fiber (100BASE-FX)
Communications protocols
Complete group of SEL protocols
(SEL ASCII, SEL Compressed ASCII, SEL Settings
File Transfer, SEL Fast Meter, SEL Fast Operate, SEL
Fast SER, RTDs, Enhanced M
IRRORED
B
ITS Communications), and Synchrophasors (SEL Fast
Message and IEEE C37.118 format), plus DNP3
Complete group of SEL protocols, Synchrophasors
(SEL Fast Message and IEEE C37.118 format), plus
DNP3 and IEC 61850
87L (line protection)
Connector type
Screw-terminal block inputs
Connectorized
®
Contact the SEL factory or your local Technical Service Center for particular
part number and ordering information (see Factory Assistance on
page P.11.46). You can also view the latest part number and ordering
information on the SEL website at www.selinc.com.