P.6.4
SEL-411L Relay Protection Manual Date Code 20151029
PC Software
ACSELERATOR QuickSet Setup
Step 2. Select the type of connection to be used: Serial, Network, or
Modem. To use the relay front-panel USB port, select Serial.
Communications parameters can be defined simultaneously for
Serial, Network, and Modem connections. The connection to be
used is selected in the Active Connection Type drop-down menu.
Step 3. Configure the PC port.
If Serial is selected as the connection type:
a. Select the port number of the PC from the Device drop-
down box.
b. Select the Data Speed for the relay serial port, or select
Auto detect to allow the software to automatically
determine the Data Speed. The default Data Speed for
the relay is 9600.
c. Select appropriate settings for Data Bits, Stop Bits,
Parity, and RTS/CTS (Hardware Handshaking)
according to the settings of the relay serial port. Default
settings are Data Bits = 8, Stop Bits = 1, Parity = N, and
RTS/CTS = OFF.
d. Enter the relay Access Level One and Access Level
Two passwords in the respective text boxes.
If Network is selected as the connection type:
a. Enter the IP address of the relay Ethernet port as the
Host IP Address
b. Enter the Telnet port number
c. Select Telnet as the File Transfer Option.
d. Enter the relay Access Level One and Access Level
Two passwords in the respective text boxes.
e. Use the Save to Address Book button to save the entered
information with a Connection Name for later use.
f. Relay Ethernet port setting ETELNET must be set to Y.
If Modem is selected as the connection type:
a. Select the port number of the PC modem from the
Device drop-down box.
b. Enter the phone number of the remote modem.
c. Select the data speed for the modem, or select Auto
detect to allow the software to automatically determine
the data speed.
d. Enter the relay Access Level One and Access Level
Two passwords in the respective text boxes.
Step 4. Click OK when finished.