Network protocols
6.3 DHCP client
SCALANCE S615 Command Line Interface
190 Configuration Manual, 06/2015, C79000-G8976-C406-02
Syntax
Call the command without parameters:
no ip dhcp config-file-request
Result
The DHCP config file request option is disabled.
Further notes
You enable the DHCP config file request option with the ip dhcp config-file-request
command.
6.3.3.3
ip dhcp client mode
Description
With this command, you configure the type of identifier with which the DHCP client logs on
with its DHCP server.
Requirement
You are in the Global Configuration mode.
The command prompt is as follows:
cli(config)#
Syntax
Call up the command with the following parameters:
ip dhcp client mode {mac|client-id<client-id>|sysname}
The parameters have the following meaning:
Parameter
Description
Range of values
mac
The client registers with its MAC address
-
client-id
The client registers with the assigned ID
-
client-id
Name of the assigned ID
max. 32 characters
sysname
The client registers with the assigned system
name
-
Result
The registration mode of the DHCP client is configured.

Table of Contents

Other manuals for Siemens SCALANCE S615

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SCALANCE S615 and is the answer not in the manual?

Siemens SCALANCE S615 Specifications

General IconGeneral
ProtocolsIPsec, OpenVPN
Power Supply24 V DC
Mounting TypeDIN Rail
Product NameSCALANCE S615
Ports5
FirewallYes
Weight0.6 kg
CertificationsCE

Related product manuals