SCALANCE S615 Command Line Interface
Configuration Manual, 06/2015, C79000-G8976-C406-02
411
Diagnostics
10
The monitoring of the system and error diagnostics are handled in different ways:
Event and fault handling:
Predefined events generate a message. These messages can be distributed in different
ways:
Entry in local logs
Transfer to the Syslog server
Sending as SNMP trap
Lighting up of the error LED
Switching at the digital output
Syslog client:
Configures the transfer to the Syslog server
10.1
Event and fault handling
In events and faults handling, you set the events whose messages will be distributed in one
of the available ways.
You configure the monitoring of certain system events and power supply and physical
interfaces in the Events configuration mode.
10.1.1
The "show" commands
This section describes commands with which you display various settings.
With the command
do [command] you can execute the "show" commands in every
configuration mode.
To do this, you replace
[command] with the "show" command that you want to execute.
Example
do show cli-console-timeout

Table of Contents

Other manuals for Siemens SCALANCE S615

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SCALANCE S615 and is the answer not in the manual?

Siemens SCALANCE S615 Specifications

General IconGeneral
ProtocolsIPsec, OpenVPN
Power Supply24 V DC
Mounting TypeDIN Rail
Product NameSCALANCE S615
Ports5
FirewallYes
Weight0.6 kg
CertificationsCE