5-49
Cisco ONS 15454 DWDM Installation and Operations Guide, R6.0
September 2005
Chapter 5 Provision Transponder and Muxponder Cards
DLP-G229 Change Card Settings for TXP_MR_2.5G and TXPP_MR_2.5G Cards
DLP-G229 Change Card Settings for TXP_MR_2.5G and TXPP_MR_2.5G Cards
Step 1 In node view, double-click the TXP_MR_2.5G or TXPP_MR_2.5G card where you want to change the
card settings.
Step 2 Click the Provisioning > Card tabs.
Step 3 Modify any of the settings described in Table 5-29.
Purpose This task changes the card settings for TXP_MR_2.5G and
TXPP_MR_2.5G transponder cards.
Tools/Equipment None
Prerequisite Procedures DLP-G46 Log into CTC, page 2-25
Required/As Needed As needed
Onsite/Remote Onsite or remote
Security Level Provisioning or higher
Table 5-29 TXP_MR_2.5G and TXPP_MR_2.5G Transponder Card Settings
Parameter Description Options
Termination
Mode
Sets the mode of operation (option only
supported for SONET/SDH payloads).
See the “16.12 Termination Modes”
section on page 16-117 for more
information.
• Transparent
• Section (ANSI) or Regeneration
Section (ETSI)
• Line (ANSI) or Multiplex Section
(ETSI)
Wavelength Sets the wavelength of the DWDM side
optical transmitter.
• First Tunable Wavelength
• Further wavelengths in 100-GHz ITU
spacing
• Supported wavelengths are in white
and marked by asterisks (**);
unsupported wavelengths are gray.
Note The four available wavelengths
are listed in the Card Parameters
section of the window and also in
the Maintenance > Info tab.