September 2005
Chapter 15 Shelf Hardware Reference
15.14.1 Alarm Contact Connections
Note The AIC-I requires a shelf assembly running Software Release 3.4.0 or later. The backplane of the ANSI
shelf contains a wire-wrap field with pin assignment according to the layout in Figure 1-21 on page 1-54.
The shelf assembly might be an existing shelf that has been upgraded to R3.4 or later. In this case the
backplane pin labeling appears as indicated in Figure 15-42 on page 15-45, but you must use the pin
assignments provided by the AIC-I as shown in Figure 1-21 on page 1-54.
Figure 15-42 ONS 15454 ANSI Backplane Pinouts
15.14.1 Alarm Contact Connections
The alarm pin field supports up to 17 alarm contacts, including four audible alarms, four visual alarms,
one alarm cutoff (ACO), and four user-definable alarm input and output contacts.
Field Pin Function Field Pin Function
BITS A1 BITS Output 2 negative (-)
ENVIR
ALARMS
OUT
N/O
A1 Normally open output pair number 1
B1 BITS Output 2 positive (+) B1
A2 BITS Input 2 negative (-) A2 Normally open output pair number 2
B2 BITS Input 2 positive (+) B2
A3 BITS Output 1 negative (-) A3 Normally open output pair number 3
B3 BITS Output 1 positive (+) B3
A4 BITS Input 1 negative (-) A4 Normally open output pair number 4
B4 BITS Input 1 positive (+) B4
LAN Connecting to a hub, or switch ACO A1 Normally open ACO pair
A1 B1
B1 CRAFT A1 Receive (PC pin #2)
A2 A2 Transmit (PC pin #3)
B2 A3 Ground (PC pin #5)
A4 DTR (PC pin #4)
LOCAL
ALARMS
AUD
(Audible)
N/O
N/O
A1 Alarm output pair number 1: Remote
audible alarm.
B1 B1
ENVIR
ALARMS
IN
A2 Alarm output pair number 2: Critical
audible alarm.
B2
A3 Alarm output pair number 3: Major
audible alarm.
A1
B3
B1
A4 Alarm output pair number 4: Minor
audible alarm.
A2
B4
B2
LOCAL
ALARMS
VIS
(Visual)
A1 Alarm output pair number 1: Remote
visual alarm.
A3
B1
A2 Alarm output pair number 2: Critical
visual alarm.
B2
A3 Alarm output pair number 3: Major
visual alarm.
B3
A4 Alarm output pair number 4: Minor
visual alarm.
B4
A1
A2
B3
A4
B4
RJ-45 pin 2 TX-
RJ-45 pin 1 TX+
RJ-45 pin 2 RX-
RJ-45 pin 1 RX+
RJ-45 pin 6 TX-
Alarm input pair number 1: Reports
closure on connected wires.
Alarm input pair number 2: Reports
closure on connected wires.
Alarm input pair number 3: Reports
closure on connected wires.
Alarm input pair number 4: Reports
closure on connected wires.
Connecting to a PC/Workstation or router
RJ-45 pin 3 TX+
B2
RJ-45 pin 3 RX+
RJ-45 pin 6 RX-
TBOS
AUDVIS
FG12FG11FG10FG9FG8FG7FG6FG5FG4FG3FG2
BITS LAN
FG1
111111111111
2222222222
3333333333
4444444444
2
3
4
2
ABABAABABABABABABABA B
LOCAL ALARMSCRAFTMODEM X . 25 ACO ENVIR ALARMS
OUTIN