Cisco ONS 15454 DWDM Installation and Operations Guide, R6.0
September 2005
Chapter 13 Maintain the Node
NTP-G115 Clean Fiber Connectors
Step 12 Replace the clean filter:
a. If the air filter is installed in the external filter brackets, slide the dry air filter all the way to the back
of the brackets to complete the procedure, continue to step 16.
b. If the filter is installed below the fan-tray assembly, remove the fan-tray assembly and slide the
dry/clean air filter into the recessed compartment at the bottom of the shelf assembly. Put the front
edge of the air filter flush against the front edge of the recessed compartment. Push the fan tray back
into the shelf assembly.
Caution If the fan tray does not slide all the way to the back of the shelf assembly, pull the fan tray out and
readjust the position of the reusable filter until the fan tray fits correctly.
Note On a powered-up ONS 15454, the fans start immediately after the fan-tray assembly is correctly
inserted.
Step 13 To verify that the tray is plugged into the backplane, ensure that the LCD on the front of the fan-tray
assembly is activated and displays node information.
Step 14 Rotate the retractable handles back into their compartments.
Step 15 If you replace the door, also reattach the ground strap.
Step 16 Close and lock the door.
Stop. You have completed this procedure.
NTP-G115 Clean Fiber Connectors
Warning
Invisible laser radiation may be emitted from the end of the unterminated fiber cable or connector. Do
not view directly with optical instruments. Viewing the laser output with certain optical instruments
(for example, eye loupes, magnifiers, and microscopes) within a distance of 100 mm may pose an eye
hazard.
Statement 1056
Purpose This procedure cleans the fiber connectors.
Tools/Equipment Inspection microscope
Compressed air/duster
Type A Fiber Optic Connector Cleaner (CLETOP reel)
Isopropyl alcohol 70 percent or higher
Optical swab
Optical receiver cleaning stick
Prerequisite Procedures None
Required/As Needed Required
Onsite/Remote Onsite
Security Level None