8-21
Cisco ONS 15454 DWDM Installation and Operations Guide, R6.0
September 2005
Chapter 8 Manage Alarms
DLP-G123 Apply Alarm Profiles to Ports
• Press the Ctrl key, and simultaneously left-click the node where the profile is to be saved.
• If you do not want to save the profile to any nodes, click Select None.
• If you want to update alarm profile information, click Synchronize.
b. Click OK.
Step 9 Return to your originating procedure (NTP).
DLP-G123 Apply Alarm Profiles to Ports
Note You can also apply alarm profiles to cards using the “DLP-G124 Apply Alarm Profiles to Cards and
Nodes” task on page 8-23.
Step 1 In node view, double-click the card that you want to change to open the card view.
Note The card view is not available for the TCC2/TCC2P card.
Step 2 Click the Provisioning > Alarm Profiles > Alarm Behavior tabs.
Figure 8-6 shows alarm profiles for the AD-1C card, for example. CTC shows Parent Card Profile:
Inherited.
Purpose This task applies a custom or default alarm severity profile to a port or
ports.
Tools/Equipment None
Prerequisite Procedures DLP-G121 Create a New or Cloned Alarm Severity Profile, page 8-17
DLP-G46 Log into CTC, page 2-25
Required/As Needed As needed
Onsite/Remote Onsite or remote
Security Level Provisioning or higher