1-19
Cisco ONS 15454 DWDM Installation and Operations Guide, R6.0
August 2005
Chapter 1      Install the Shelf and Common Control Cards
DLP-G8 Install the Air Ramp
Figure 1-5 Mounting the Air Ramp in a Rack
Step 4
Repeat this task for every shelf assembly you need to install.
Step 5 Return to your originating procedure (NTP).
DLP-G8 Install the Air Ramp
Step 1 The air ramp requires 1 RU in a standard 19-inch (482.6-mm) or 23-inch (584.2-mm) rack. Locate the 
RMU space specified in your site plan. See the “15.5 Typical DWDM Rack Layouts” section on 
page 15-17 for more information about air ramp placement.
Step 2 Verify that the mounting brackets attached to the unit are correct for your rack size. Complete the  
“DLP-G3 Reverse the Mounting Bracket to Fit a 19-inch (482.6-mm) Rack (ANSI Only)” task on 
page 1-10 as required.
Purpose Use this task to install the air ramp.
Tools/Equipment #2 Phillips screwdriver
Prerequisite Procedures None
Required/As Needed As needed
Onsite/Remote Onsite
Security Level None
61582
Equipment rack