108 Pre-Configured Alarms
Alarm Type Description
Security Security alarms are for certificate expiry events. This includes warnings 30 days before a certificate is set to
expire and when an expired certificate is installed.
Services Service alarms are for events related to RUGGEDCOM ROX II services, such as time services, link failover,
Dynamic Domain Name Server (DNS) etc.
CONTENTS
• Section5.7.1, “Pre-Configured Alarms”
• Section5.7.2, “Viewing a List of Active Alarms”
• Section5.7.3, “Clearing and Acknowledging Alarms”
• Section5.7.4, “Configuring an Alarm”
Section5.7.1
Pre-Configured Alarms
RUGGEDCOM ROX II is equipped with a series of pre-configured alarms designed to monitor and protect the
device.
Alarm Type Alarm Description Suggested Resolution
Admin Featurekey mismatch The featurekey does not match the
serial numbers for the control module
and backplane hardware.
Move the featurekey to the correct
device with the matching hardware or
request an updated key from Siemens
Customer Support.
Admin Featurekey partial mismatch The featurekey does not match the
serial number for either the control
module or backplane hardware.
Move the featurekey to the correct
device with the matching hardware or
request an updated key from Siemens
Customer Support.
Chassis PM1 bad supply Input power to the power module is
outside nominal operating range.
Make sure the input power operating
range meets the device requirements.
Chassis PM2 bad supply Input power to the power module is
outside nominal operating range.
Make sure the input power operating
range meets the device requirements.
Chassis PM1 MOV protection bad The Metal Oxide Varistor (MOV)
protection component within the PM1
power module is damaged.
Contact Siemens Customer Support to
return the power module.
Chassis PM2 MOV protection bad The Metal Oxide Varistor (MOV)
protection component within the PM2
power module is damaged.
Contact Siemens Customer Support to
return the power module.
Chassis Real-time clock battery low The Real-Time Clock (RTC) battery in
the control module is depleted.
Contact Siemens Customer Support to
return the device for repair.
Chassis LM Watchdog Failure The specified line module has stopped
sending its heartbeat message to the
control module.
Inspect the line module to make sure
it is functioning properly.
Chassis Fan-Controller Hardware Failure (For
MX5000RE Only)
The fan tray is damaged. One or more
fan trays may stop spinning.
Contact Siemens Customer Support to
return the fan module.
Chassis Fan-Controller Overtemp (For
MX5000RE Only)
The ambient temperature within the
RuggedEnclosure has exceeded the
Power down the device until the
ambient temperature has cooled.