SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
1037
4 Faults and alarms
4.2 List of faults and alarms
F31912 Encoder 1: Device combination is not permissible
Message value: %1
Message class: Error in the parameterization / configuration / commissioning procedure (18)
Drive object: DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S
Reaction: ENCODER (IASC/DCBRK, NONE)
Acknowledge: PULSE INHIBIT
Cause: The selected device combination is not supported.
Fault value (r0949, interpret decimal):
1003:
The connected measuring unit cannot be operated with the EnDat 2.2 converter. For instance, the measuring unit
has a pulse number/resolution of 2^n.
1005:
The type of measuring unit (incremental) is not supported by the EnDat 2.2 converter.
1006:
The maximum duration (31.25 µs) of the EnDat transfer was exceeded.
2001:
The set combination of current controller cycle, DP cycle and Safety cycle is not supported by the EnDat 2.2
converter.
2002:
The resolution of the linear measuring unit does not match the pole pair width of the linear motor
Remedy: Re fault value = 1003, 1005, 1006:
- Use a measuring unit that is permissible.
For fault value = 2001:
- Set a permissible cycle combination (if required, use standard settings).
For fault value = 2002:
- Use a measuring unit with a lower resolution (p0422).
A31915 (F, N) Encoder 1: Configuration error
Message value: %1
Message class: Error in the parameterization / configuration / commissioning procedure (18)
Drive object: DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S
Reaction: NONE
Acknowledge: NONE
Cause: The configuration for encoder 1 is incorrect.
Alarm value (r2124, interpret decimal):
1:
Re-parameterization between fault/alarm is not permissible.
419:
When the fine resolution Gx_XIST2 is configured, the encoder identifies a maximum possible absolute position actual
value (r0483) that can no longer be represented within 32 bits.
Remedy: Re alarm value = 1:
No re-parameterization between fault/alarm.
Re alarm value = 419:
Reduce the fine resolution (p0419) or deactivate the monitoring (p0437.25), if the complete multiturn range is not
required.
Reaction upon F: NONE (ENCODER, IASC/DCBRK)
Acknowl. upon F: IMMEDIATELY
Reaction upon N: NONE
Acknowl. upon N: NONE

Table of Contents

Other manuals for Siemens SINAMICS DCM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS DCM and is the answer not in the manual?

Siemens SINAMICS DCM Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS DCM
CategoryMedia Converter
LanguageEnglish

Related product manuals