SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
185
2 Parameters
2.2 List of parameters
Description: Sets the time constant for the actual value filter (PT1) of the technology controller.
Description: Display and connector output for the smoothed actual value after the filter (PT1) of the technology controller.
Description: Sets the upper limit for the actual value signal of the technology controller.
Dependency: Refer to: p2252, p2264, p2265, p2271
Notice: If the actual value exceeds this upper limit, this results in fault F07426.
Note: Limiting only active for p2252.3 = 1.
Description: Sets the lower limit for the actual value signal of the technology controller.
Dependency: Refer to: p2264, p2265, p2271
Notice: If the actual value falls below this lower limit, this results in fault F07426.
Note: Limiting only active for p2252.3 = 1.
Description: Sets the scaling factor for the actual value of the technology controller.
Dependency: Refer to: p2264, p2265, p2267, p2268, p2271
p2265 Technology controller actual value filter time constant / Tec_ctrl act T
DC_CTRL (Tech_ctrl),
DC_CTRL_R
(Tech_ctrl),
DC_CTRL_R_S
(Tech_ctrl),
DC_CTRL_S
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 7958
P-Group: Technology Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.000 [s] 60.000 [s] 0.000 [s]
r2266 CO: Technology controller actual value after filter / Tec_ctr act aftFlt
DC_CTRL (Tech_ctrl),
DC_CTRL_R
(Tech_ctrl),
DC_CTRL_R_S
(Tech_ctrl),
DC_CTRL_S
(Tech_ctrl)
Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 7958
P-Group: Technology Unit group: 9_1 Unit selection: p0595
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
p2267 Technology controller upper limit actual value / Tec_ctrl u_lim act
DC_CTRL (Tech_ctrl),
DC_CTRL_R
(Tech_ctrl),
DC_CTRL_R_S
(Tech_ctrl),
DC_CTRL_S
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 7958
P-Group: Technology Unit group: 9_1 Unit selection: p0595
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
-200.00 [%] 200.00 [%] 200.00 [%]
p2268 Technology controller lower limit actual value / Tec_ctrl l_lim act
DC_CTRL (Tech_ctrl),
DC_CTRL_R
(Tech_ctrl),
DC_CTRL_R_S
(Tech_ctrl),
DC_CTRL_S
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 7958
P-Group: Technology Unit group: 9_1 Unit selection: p0595
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
-200.00 [%] 200.00 [%] -200.00 [%]
p2269 Technology controller gain actual value / Tech_ctrl gain act
DC_CTRL (Tech_ctrl),
DC_CTRL_R
(Tech_ctrl),
DC_CTRL_R_S
(Tech_ctrl),
DC_CTRL_S
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 7958
P-Group: Technology Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [%] 500.00 [%] 100.00 [%]