Description: Display and connector output of the setpoint dependent upon oscillation selection.
Note: If oscillation is selected (p50485 = 1 signal):
r52208 = r52203
If oscillation is de-selected (p50485 = 0 signal):
r52208 = p50484
Description: Display and connector output of the sum of all fixed setpoints following selection of at least one connector.
Dependency: Refer to: p50430, p50431
Note: If at least one connector has been selected via p50430[0 to 7]:
r52209 = r52204
If no connectors have been selected via p50430[0 to 7]:
r52209 = r52210
Description: Display and connector output for the signals interconnected and inverted via connector input p50632[0 to 3].
Index: [0] = Signal p50632[0] inverted
[1] = Signal p50632[1] inverted
[2] = Signal p50632[2] inverted
[3] = Signal p50632[3] inverted
Description: Display and connector output for the fixed setpoint after intervention from the advanced operator panel 30 (AOP30).
Dependency: Refer to: p50433
r52208 CO: Oscillation output after selection / Oscil outp aft sel
DC_CTRL Can be changed: - Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 3120
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
r52209 CO: Fixed setpoint output after selection / Fix set outp
DC_CTRL Can be changed: - Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 3115
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
r52210[0...3] CO: RFG positive limiting inverted after RFG / RFG pos lim inv
DC_CTRL Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 3155
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
r52211 CO: Fixed setpoint output after AOP30 / Fix set outp AOP
DC_CTRL Can be changed: - Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 3113
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]