SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
181
2 Parameters
2.2 List of parameters
Description: Displays the system runtime in days when the alarm was cleared.
Dependency: Refer to: r2110, r2114, r2122, r2123, r2124, r2125, r2134, r2145, r3121, r3123
Notice: The time comprises r2146 (days) and r2125 (milliseconds).
Note: The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
Description: Setting to delete the fault buffer of all existing drive objects.
Value: 0: Inactive
1: Start to delete the fault buffer of all drive objects
Dependency: Refer to: r0945, r0947, r0948, r0949, r2109, r2130, r2133, r2136
Note: p2147 is automatically set to 0 after execution.
Description: Display and BICO output for the first status word of the monitoring functions.
Description: Display and BICO output for the third status word of the monitoring functions.
r2146[0...63] Alarm time removed in days / t_alarm res days
All objects Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: 8065
P-Group: Messages Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
p2147 Delete fault buffer of all drive objects / Del fault buffer
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: U, T Calculated: - Access level: 4
Data type: Integer16 Dyn. index: - Func. diagram: 8060
P-Group: Displays, signals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
r2197.3...7 CO/BO: Status word monitoring 1 / ZSW monitor 1
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: 2534
P-Group: Messages Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
03 n_act >= 0 Yes No 8011
07 Speed setp - act val deviation in tolerance
t_off
Yes No 8011
r2199.1 CO/BO: Status word monitoring 3 / ZSW monitor 3
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: 2537
P-Group: Messages Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
01 f or n comparison value reached or
exceeded
Yes No 8010