2 Parameters
2.2 List of parameters
SINAMICS DCM
500 List Manual (LH8), 02/2015, 6RX1800-0ED76
Description: Sets the type for analog input 0 (X177.25/26) on the CUD.
Value: 0: Bipolar voltage input (-10 V ... +10 V)
1: Bipolar current input (-20 mA to +20 mA)
2: Unipolar current input monitored (+4 mA to +20 mA)
Note: AI: Analog Input
Description: Sets the scaling for analog input 0 (X177.25/26) on the CUD.
The value indicates the percentage value for the mapping of an input voltage of 10 V or an input current of 20 mA at
the analog input.
Example:
p50701 = 90%
--> 10 V or 20 mA is scaled to 90%
--> 5 V or 10 mA is equivalent to 45%
Description: Sets the offset for analog input 0 (X177.25/26) on the CUD.
Description: Sets the signal processing mode for analog input 0 (X177.25/26) on the CUD.
Value: 0: Signal not controlled
1: Signal absolute value generation
2: Signal inverted
3: Signal absolute value generation inverted
p50700 CUD analog input 0 type / CUD AI 0 type
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: 2075
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 2 0
p50701[0...n] CUD analog input 0 scaling / CUD AI 0 scal
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 2075
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
-1000.0 [%] 1000.0 [%] 100.0 [%]
p50702 CUD analog input 0 offset / CUD AI 0 offs
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 2075
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
-200.00 [%] 200.00 [%] 0.00 [%]
p50703 CUD analog input 0 signal processing / CUD AI 0 sig proc
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: 2075
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 3 0