2 Parameters
2.2 List of parameters
SINAMICS DCM
498 List Manual (LH8), 02/2015, 6RX1800-0ED76
Description: Sets the signal source for feedback from the line contactor.
The feedback signal is checked and fault F60104 is triggered in the following cases:
- If, following power-up, a 1 signal is not detected within the time set in p50095 (in other words, if the line contactor
has not closed).
- If a 0 signal is detected during operation.
Note: Feedback from the line contactor can be achieved by integrating one of the line contactor's auxiliary contacts into the
device control.
Description: Sets the signal source for the selection of standstill field injection.
Dependency: Refer to: F60045
Description: Sets the signal source to enable the EMF controller.
Description: Sets the signal source to enable the torque limits to be changed over.
Dependency: Refer to: p50180, p50181, p50182, p50183
Note: 1 signal: Changeover enabled
0 signal: Changeover disabled
p50691[0...n] BI: Sequence control line contactor feedback / Line cont feedb
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: 2651
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 1
p50692[0...n] BI: Cl-loop field curr ctrl sig source for inject of standst field / If_ctr stst sig s
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: 6910, 8046
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p50693[0...n] BI: EMF controller enable signal source / EMF ctr ena sig s
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: 6900
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 1
p50694[0...n] BI: Torque limiting signal source to enable changeover / T lim ch ena sig s
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: 6825
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0