4 Faults and alarms
4.2 List of faults and alarms
10 (= 0A hex):
The sign-of-life bit in the receive telegram is not set.
11 (= 0B hex):
Synchronization error during alternating cyclic data transfer.
16 (= 10 hex):
The receive telegram is too early.
32 (= 20 hex):
Error in the telegram header.
33 (= 21 hex):
The cyclic telegram has not been received.
34 (= 22 hex):
Timeout in the telegram receive list.
35 (= 23 hex):
Receive error: The telegram buffer memory contains an error.
64 (= 40 hex):
Timeout in the telegram send list.
65 (= 41 hex):
Telegram type does not match send list.
66 (= 42 hex):
Send error: The telegram buffer memory contains an error.
67 (= 43 hex):
Send error: The telegram buffer memory contains an error.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy: - check the electrical cabinet design and cable routing for EMC compliance
- check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
See also: p9916 (DRIVE-CLiQ data transfer error shutdown threshold slave)
F30845 Power unit DRIVE-CLiQ: Cyclic data transfer error
Message value: Component number: %1, fault cause: %2
Message class: Internal (DRIVE-CLiQ) communication error (12)
Drive object: DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S
Reaction: OFF2
Acknowledge: IMMEDIATELY
Cause: A DRIVE-CLiQ communication error has occurred from the Control Unit to the power unit concerned.
Fault cause:
11 (= 0B hex):
Synchronization error during alternating cyclic data transfer.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy: Carry out a POWER ON (power off/on).
See also: p9916 (DRIVE-CLiQ data transfer error shutdown threshold slave)
F30850 Power unit: Internal software error
Message value: %1
Message class: Hardware / software error (1)
Drive object: DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S
Reaction: OFF1 (NONE, OFF2, OFF3)
Acknowledge: POWER ON
Cause: An internal software error has occurred in the power unit.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.