SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
477
2 Parameters
2.2 List of parameters
Description: Sets the x coordinate for pair of values 2 for adaptation of the droop.
Notice: The following condition applies for x coordinate 1/2:
p50558 < p50561
Note: The adaptation of the droop is defined using 2 pairs of values.
Pair of values 1:
p50558/p50552 (x/y coordinate)
Pair of values 2:
p50561/p50227 (x/y coordinate)
Description: Sets positive limiting for the droop on the speed controller.
Dependency: Refer to: p50563
Description: Sets negative limiting for the droop on the speed controller.
Dependency: Refer to: p50562
Description: Sets the base speed for the frequency response plot for the optimization run "Speed control optimization for drives
that are capable of oscillation" (p50051 = 29).
Dependency: Refer to: p50566, p50567
p50561[0...n] Speed controller adaptation droop x coordinate 2 / Adapt droop x2
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6805
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
0.00 [%] 100.00 [%] 0.00 [%]
p50562[0...n] Speed controller droop positive limiting / Droop pos lim
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6805
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
0.00 [%] 200.00 [%] 100.00 [%]
p50563[0...n] Speed controller droop negative limiting / Droop neg lim
DC_CTRL Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6805
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
-200.00 [%] 0.00 [%] -100.00 [%]
p50565 Speed controller optimization frequency response plot base speed / f_plot n_base
DC_CTRL Can be changed: T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 2660
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
1.0 [%] 30.0 [%] 20.0 [%]