SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
571
2 Parameters
2.2 List of parameters
Description: Display and connector output for the active power for a pure ohmic load (= r52126 * r52127).
The value is averaged over six firing cycles.
Note: This quantity is used for heating applications (rms value current control or rms value power control).
Description: Display and connector output for the current controller setpoint after reduced gearbox stressing.
Description: Display and connector output for the rms value of the internal armature current actual value.
The value is averaged over 6 firing cycles, and referred to the rated device current (r50072[1]).
Description: Display and connector output for the rms value of the armature voltage.
The value is averaged over six firing cycles.
100 % corresponds to (3 * sqrt(2)) / Pi * p50078[0] = 1.35 * p50078[0] (= U_di0_rated)
Description: Displays the linearized firing angle.
Dependency: Refer to: p50600
r52124 CO: Active power for a pure ohmic load / P_act ohm load
DC_CTRL Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6902
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
r52125 CO: Curr limitation arm curr setpoint aft reduced gearbox stressing / Ia set aft gear
DC_CTRL Can be changed: - Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6845
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
r52126 CO: Armature current actual value rms value / Ia_act rms
DC_CTRL Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6851
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
r52127 CO: Armature voltage rms value / Ua_act rms
DC_CTRL Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6902
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
r52128 CO: Firing angle linearized / Firing angle lin
DC_CTRL Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6858
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]