2 Parameters
2.2 List of parameters
Description: Displays the application-specific view of the individual drive object.
Dependency: Refer to: p0107, r0107
Description: Setting to activate/de-activate a drive object.
Value: 0: De-activate drive object
1: Activate drive object
Dependency: Refer to: r0106
Notice: The following applies when activating:
If components are inserted for the first time and the appropriate drive object is activated, then the drive system is
automatically booted. To do this, the pulses of all of the drive objects must be suppressed.
Description: Setting to activate/de-activate a drive object.
Value: 0: De-activate drive object
1: Activate drive object
2: Drive object de-activate and not present
Recommendation: After inserting all of the components of a drive object, before activating, first wait for Alarm A01316.
Dependency: Refer to: r0106
Notice: The following applies when activating:
If components are inserted for the first time and the appropriate drive object is activated, then the drive system is
automatically booted. To do this, the pulses of all of the drive objects must be suppressed.
Description: Setting to activate/de-activate a drive object.
Value: 0: De-activate drive object
1: Activate drive object
2: Drive object de-activate and not present
r0103 Application-specific view / Appl_spec view
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Closed-loop control Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 65535 -
p0105 Activate/de-activate drive object / DO act/deact
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed: U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Closed-loop control Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 1
p0105 Activate/de-activate drive object / DO act/deact
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Closed-loop control Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 2 1
p0105 Activate/de-activate drive object / DO act/deact
TM150, TM15DI_DO Can be changed: T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Closed-loop control Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 2 1