2 Parameters
2.2 List of parameters
SINAMICS DCM
154 List Manual (LH8), 02/2015, 6RX1800-0ED76
Description: Setting to invert the individual binector inputs of the binector connector converter.
Index: [0] = Status word 1
[1] = Status word 2
[2] = Free status word 3
[3] = Free status word 4
[4] = Free status word 5
Dependency: Refer to: p2080, p2081, p2082, p2083, r2089
Description: Connector output to interconnect the status words to a PZD send word.
Index: [0] = Status word 1
[1] = Status word 2
[2] = Free status word 3
[3] = Free status word 4
[4] = Free status word 5
p2088[0...4] Invert binector-connector converter status word / Bin/con ZSW inv
All objects Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: 2472
P-Group: Communications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 0000 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Bit 0 Inverted Not inverted -
01 Bit 1 Inverted Not inverted -
02 Bit 2 Inverted Not inverted -
03 Bit 3 Inverted Not inverted -
04 Bit 4 Inverted Not inverted -
05 Bit 5 Inverted Not inverted -
06 Bit 6 Inverted Not inverted -
07 Bit 7 Inverted Not inverted -
08 Bit 8 Inverted Not inverted -
09 Bit 9 Inverted Not inverted -
10 Bit 10 Inverted Not inverted -
11 Bit 11 Inverted Not inverted -
12 Bit 12 Inverted Not inverted -
13 Bit 13 Inverted Not inverted -
14 Bit 14 Inverted Not inverted -
15 Bit 15 Inverted Not inverted -
r2089[0...4] CO: Send binector-connector converter status word / Bin/con ZSW send
All objects Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: 2472
P-Group: Communications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Bit 0 ON OFF -
01 Bit 1 ON OFF -
02 Bit 2 ON OFF -
03 Bit 3 ON OFF -
04 Bit 4 ON OFF -
05 Bit 5 ON OFF -
06 Bit 6 ON OFF -
07 Bit 7 ON OFF -
08 Bit 8 ON OFF -
09 Bit 9 ON OFF -
10 Bit 10 ON OFF -
11 Bit 11 ON OFF -
12 Bit 12 ON OFF -

Table of Contents

Other manuals for Siemens SINAMICS DCM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS DCM and is the answer not in the manual?

Siemens SINAMICS DCM Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS DCM
CategoryMedia Converter
LanguageEnglish

Related product manuals