4 Faults and alarms
4.2 List of faults and alarms
47: Analog input XT1.103/104, voltage input, -270 V incorrect value
48: Analog input XT1.103/104, voltage input, reference value incorrect
49: Analog output 0 (X177.49/50), offset incorrect value
50: Analog output 0 (X177.49/50), -10 V incorrect value
51: Analog output 0 (X177.49/50), +10 V incorrect value
52: Analog output 0 (X177.49/50), reference value incorrect
53: Analog output 1 (X177.51/52), offset incorrect value
54: Analog output 1 (X177.51/52), -10 V incorrect value
55: Analog output 1 (X177.51/52), +10 V incorrect value
56: Analog output 1 (X177.51/52), reference value incorrect
Note:
r50047[1]: Incorrect calibration value
Remedy: Replace the electronics module with the incorrect calibration values.
Reaction upon N: NONE
Acknowl. upon N: NONE
Reaction upon A: NONE
Acknowl. upon A: NONE
F60064 (N, A) Error communicating with second processor TMS320
Message value: -
Message class: Internal (DRIVE-CLiQ) communication error (12)
Drive object: DC_CTRL
Reaction: OFF2 (NONE)
Acknowledge: IMMEDIATELY
Cause: Communication with the second processor (TMS320) has failed.
Note:
r50047[1]: Communication counter in send direction
r50047[2]: Communication counter in receive direction
Remedy: Carry out a POWER ON (power off/on) for all components.
Reaction upon N: NONE
Acknowl. upon N: NONE
Reaction upon A: NONE
Acknowl. upon A: NONE
F60065 (N, A) Software update on second processor (TMS320) failed
Message value: %1
Message class: Hardware/software error (1)
Drive object: DC_CTRL
Reaction: OFF2 (NONE)
Acknowledge: IMMEDIATELY
Cause: The updating of the software for the second processor (TMS320) has failed.
Fault value (r0949, interpret decimal):
This value indicates the state in which the fault occurred.
2: Wait for the TMS320 bootloader to be ready.
3: Check the version of the TMS320 bootloader.
4: Check the version of the TMS320 application software.
5: Wait for the TMS320 to exit the bootloader.
6: Wait for theTMS320 to load its Flash API.
7: Wait for theTMS320 to delete its Flash EPROM.
8: Send a section of code 8 KB in size to the TMS320.
9: Wait for the TMS320 to request a new 8 KB section of code.
10: Wait until the TMS320 application software has been started.
11: Wait until the TMS320 is ready for a new command.

Table of Contents

Other manuals for Siemens SINAMICS DCM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS DCM and is the answer not in the manual?

Siemens SINAMICS DCM Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS DCM
CategoryMedia Converter
LanguageEnglish

Related product manuals