SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
227
2 Parameters
2.2 List of parameters
Description: Sets the delay time for wire-breakage monitoring of the analog inputs on Terminal Module 31 (TM31).
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Description: Sets the offset for the analog inputs of Terminal Module 31 (TM31).
The offset is added to the input signal before the scaling characteristic.
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Description: Activates the absolute value generation for the analog input signals of Terminal Module 31 (TM31).
Value: 0: No absolute value generation
1: Absolute value generation switched in
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Description: Sets the signal source to invert the analog inputs signals of Terminal Module 31 (TM31).
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
p4062[0...1] TM31 analog inputs wire breakage monitoring delay time / TM31 wirebrk t_del
TM31 Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: 9566, 9568
P-Group: Terminals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 1000 [ms] 100 [ms]
p4063[0...1] TM31 analog inputs offset / TM31 AI offset
TM31 Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 9566, 9568
P-Group: Terminals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-20.000 20.000 0.000
p4066[0...1] TM31 analog inputs activate absolute value generation / TM31 AI absVal act
TM31 Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: 9566, 9568
P-Group: Terminals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p4067[0...1] BI: TM31 analog inputs invert signal source / TM31 AI inv s s
TM31 Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 9566, 9568
P-Group: Terminals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0