2 Parameters
2.2 List of parameters
SINAMICS DCM
80 List Manual (LH8), 02/2015, 6RX1800-0ED76
Dependency: Refer to: p0404
Note: ZM: Zero mark
This parameter is only used for diagnostics.
A value of zero is displayed if an encoder is not present.
Re bit 20, 21 (voltage level 5 V, voltage level 24 V):
The voltage level cannot be detected. Therefore, these bits are always set to 0.
Description: Displays the encoder configuration supported by the Sensor Module.
Index: [0] = Encoder 1
[1] = Encoder 2
[2] = -
Dependency: Refer to: p0404
Note: ZM: Zero mark
This parameter is only used for diagnostics.
A value of zero is displayed if an encoder is not present.
Description: Sets the Sensor Module configuration.
17 Track A/B analog Yes No -
20 Voltage level 5 V Yes No -
21 Voltage level 24 V Yes No -
22 Remote sense (only SMC30) Yes No -
23 Resolver excit Yes No -
r0456[0...2] Encoder configuration supported / Enc_config supp
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Encoder Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Linear encoder Yes No -
01 Absolute encoder Yes No -
02 Multiturn encoder Yes No -
03 Track A/B sq-wave Yes No -
04 Track A/B sine Yes No -
05 Track C/D Yes No -
06 Hall sensor Yes No -
08 EnDat encoder Yes No -
09 SSI encoder Yes No -
10 DRIVE-CLiQ encoder Yes No -
11 Digital encoder Yes No -
12 Equidistant zero mark Yes No -
13 Irregular zero mark Yes No -
14 Distance-coded zero mark Yes No -
15 Commutation with zero mark (not ASM) Yes No -
16 Acceleration Yes No -
17 Track A/B analog Yes No -
20 Voltage level 5 V Yes No -
21 Voltage level 24 V Yes No -
22 Remote sense (only SMC30) Yes No -
23 Resolver excit Yes No -
r0458[0...2] Sensor Module properties / SM properties
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: 4704
P-Group: Encoder Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -